Diesel Generator Set Parameters
| Model | KPS-C1000 | Fuel Consumption at 75% Load | 180 liters per hour |
| Standby Power Output | 1000 Kw / 1250 Kva | Fuel Consumption at 100% Load | 256 liters per hour |
| Prime Power Output | 900 Kw / 1125 Kva | Lubricating Oil Capacity | 135 liters |
| Voltage Output | 380V / 50Hz | Coolant Capacity | 336 liters |
| Engine Brand | Cummins | Combustion Air Intake | 1309 liters per sec |
| Engine Model | KTA38-G9 | Exhaust Gas Flow | 3540 liters per sec |
| Number of Cylinders | V12 | Exhaust Temperature (at Full Load) | 529 ℃ |
| Aspiration Method | Turbocharged | Net Engine Power – Standby | 1089 kwm |
| Bore x Stroke | 159 mm x 159 mm | Net Engine Power – Prime | NA |
| Compression Ratio | 13.9 : 1 | Dimensions Length | 4400 mm |
| Displacement | 37.8 liters | Width | 2100 mm |
| Rated Speed | 1500 rpm | Height | 2200 mm |
| Starting Voltage | DC 24V | Genset Weight | 8800 kg |
Standby Power
Used for temporary emergency applications. The generator can only operate up to the rated output and is limited to a maximum of 500 hours per year. Overload operation is not permitted under this category.
Prime Power
Suitable for variable load operation. The average load within a 24-hour period should not exceed 80% of the rated output. Overload operation of up to 10% above the rated output is allowed for 1 hour every 12 hours of operation.
Note: Our company reserves the right to modify product design and technical specifications without prior notice.