Diesel Generator Set Parameters
Model | KPS-C1340 | Fuel Consumption at 75% Load | 238 liters per hour |
Standby Power Output | 1340 Kw / 1675 Kva | Fuel Consumption at 100% Load | 309 liters per hour |
Prime Power Output | 1120 Kw / 1400 Kva | Lubricating Oil Capacity | 204 liters |
Voltage Output | 380V / 50Hz | Coolant Capacity | 400 liters |
Engine Brand | Cummins | Combustion Air Intake | 1500 liters per sec |
Engine Model | KTA50-G8 | Exhaust Gas Flow | 3845 liters per sec |
Number of Cylinders | V16 | Exhaust Temperature (at Full Load) | 482 ℃ |
Aspiration Method | Turbocharged | Net Engine Power – Standby | 1429 kwm |
Bore x Stroke | 159 mm x 159 mm | Net Engine Power – Prime | 1200 kwm |
Compression Ratio | 14.9 : 1 | Dimensions Length | 5100 mm |
Displacement | 50.3 liters | Width | 2250 mm |
Rated Speed | 1500 rpm | Height | 2500 mm |
Starting Voltage | DC 24V | Genset Weight | 11300 Kg |
Standby Power
Used for temporary emergency applications. The generator can only operate up to the rated output and is limited to a maximum of 500 hours per year. Overload operation is not permitted under this category.
Prime Power
Suitable for variable load operation. The average load within a 24-hour period should not exceed 80% of the rated output. Overload operation of up to 10% above the rated output is allowed for 1 hour every 12 hours of operation.
Note: Our company reserves the right to modify product design and technical specifications without prior notice.