Diesel Generator Set Parameters
Model | KPS-C1120 | Fuel Consumption at 75% Load | 199 liters per hour |
Standby Power Output | 1120 Kw / 1400 Kva | Fuel Consumption at 100% Load | 261 liters per hour |
Prime Power Output | 1000 Kw / 1250 Kva | Lubricating Oil Capacity | 177 liters |
Voltage Output | 380V / 50Hz | Coolant Capacity | 351 liters |
Engine Brand | Cummins | Combustion Air Intake | 1605 liters per sec |
Engine Model | KTA50-G3 | Exhaust Gas Flow | 3728 liters per sec |
Number of Cylinders | V16 | Exhaust Temperature (at Full Load) | 518 ℃ |
Aspiration Method | Turbocharged | Net Engine Power – Standby | 1227 kwm |
Bore x Stroke | 159 mm x 159 mm | Net Engine Power – Prime | 1150 kwm |
Compression Ratio | 13.9 : 1 | Dimensions Length | 4900 mm |
Displacement | 50.3 liters | Width | 2100 mm |
Rated Speed | 1500 rpm | Height | 2400 mm |
Starting Voltage | DC 24V | Genset Weight | 9800 公斤 |
Standby Power
Used for temporary emergency applications. The generator can only operate up to the rated output and is limited to a maximum of 500 hours per year. Overload operation is not permitted under this category.
Prime Power
Suitable for variable load operation. The average load within a 24-hour period should not exceed 80% of the rated output. Overload operation of up to 10% above the rated output is allowed for 1 hour every 12 hours of operation.
Note: Our company reserves the right to modify product design and technical specifications without prior notice.